System Specifications
380, 400, 440 or 480 Volts and Medium Voltage Up To 25kV Rated Voltage
50Hz or 60Hz Rated Frequency
+ Input Specifications Click to expand
+ Output Specifications Click to expand
+ 1% Output voltage steady state conditions
+ 5% Output voltage during dynamic conditions, < 1 second
(With maximum 50% load step)
+ 0.5% Output frequency steady state conditions
1% Output frequency during dynamic conditions, < 1 second
(With maximum 50% load step)
0.8 Design output power factor
20 x In Max. current during down-stream short circuit
1.5%, 2.5%(Ph-N) Harmonic distortion factor
10% for 1 hour Overload capacity in normal operation
100% Load unbalanced capability
2% Voltage system symmetry
K Radio interference level
+ Ambient Conditions Click to expand
45°C (113°F) Maximum ambient temperature
(For higher ambient temperatures certain de-rating factors may need to be applied)
90% non condensing Humidity
500 meters (1640 feet) above sea level Maximum Altitude
(For higher altitudes certain de-rating factors may need to be applied)